Siphon Selection

Pick the siphon that doses the absorption area.

When you see this page

The page follows Siphon Plumbing when the design uses siphon delivery, which happens when the bed is more than 10 ft below the dosing tank. A siphon needs no electricity. Tank Selection comes next.

The list

  • The Siphons list is grouped by manufacturer. You select one siphon.
  • On a first visit the first siphon that qualifies is selected. Your choice is kept on later visits unless the persona changes.
  • Siphons that don’t qualify are greyed out, with the reason in brackets.

Which siphons qualify

A siphon must pass these checks:

  1. Fall: the fall from the siphon to the laterals, less pipe friction, must be at least 3 ft plus the persona’s Minimum head surplus.
  2. Head at the holes (elevated sand mounds and at-grades): the head at the last hole of the lowest-head lateral must be at least 3 ft (§73.44(b)(11)), while the holes pass the siphon’s average discharge. Each hole passes 11.82 × d² × √h gpm, so the more holes the design has, the less head each one gets. With 5⁄16 in. holes, a siphon can feed at most (its average discharge in gpm ÷ 2.0) holes. For a Fluid Dynamics 207 that is 15. Larger holes only lower the head, so if 5⁄16 in. fails, the siphon fails.
  3. Minimum discharge: the design flow rate must be at least the siphon’s minimum discharge.
  4. Flow match: the design flow rate must be between 80% and 120% of the siphon’s average discharge.
Reason shown Failed check
insufficient head 1
head at the holes 2.64 ft, under 3 ft 2 (with the design’s own figure)
flow rate < min 3
flow rate too low 4
flow rate too high 4

The summary panel shows the plumbing calculation for the selected siphon.

In the report

The siphon head itemization in Supporting Calculations has two head rows:

  • Minimum height siphon intake above lateral: the fall from the siphon to the laterals.
  • Calculated terminal head: for elevated sand mounds and at-grades, the head at the last hole of the lowest-head lateral (check 2). It is always at least 3 ft on a design that qualifies. Until November 2026 this row showed the fall less pipe friction instead.

Saved designs

A saved design whose siphon now fails check 2 shows the This design needs to be checked warning when you open it, for example Fluid Dynamics 207: its plumbing check fails (head at the holes 2.64 ft, under 3 ft). Walk it through the wizard and pick a siphon that qualifies, or change the system. See Managing your saved designs.

Siphon types

  • Fixed drawdown (Fluid Dynamics): the drawdown is set by the siphon. The dosing tank needs enough inside area for it, and a trap (270° elbow) is added.
  • Adjustable drawdown (Flout): the drawdown is set within a range. An in-tank vent is added instead of a trap.

Messages

  • Select a siphon!
  • No siphon in the catalogue suits this design. A pump can dose it instead: place the dosing tank no more than 10 ft above the absorption area (Elevation change on Discharge Delivery). Or pick another system. Shown when you press Next and every siphon is greyed out. The wizard uses a pump instead of a siphon once the elevation change is 10 ft down or less.

Tips

  • If every siphon shows head at the holes … under 3 ft, the design has too many holes for any siphon. A pump can dose it.
  • If no dosing tank qualifies on Tank Selection, a fixed-drawdown siphon may need a tank with more inside area. Try another siphon.

Discharge Delivery, Siphon Plumbing, Tank Selection.